4 BY 2 FORMAT POINT ID REPORTING CODES
4 BY 2 FORMAT POINT ID ALARM REPORT CODES
Refer to the 4 by 2 Format Point ID Reporting
Code table to view/edit the alarm reporting codes
for each of the 12 sensors. The communicator will
send these codes if Point ID is enabled and any
sensor triggers an alarm. The factory settings are
listed, along with a blank area to write in the new
installation values.
Use program Steps #210 - 233 to change the 4 by 2
Point ID alarm reporting codes.
NOTE: Be careful not to duplicate codes unless the
Central Station requires specifi c codes for certain
types of sensors.
STEPS #210-233
Any value from 0-99 can be programmed for each
event using these steps (enter “0” to stop an event
from reporting).
4 BY 2 FORMAT POINT ID TROUBLE REPORT CODES
Refer to the 4 by 2 Format Point ID Reporting Code
table to view/edit the trouble reporting codes for
each of the 12 sensors. The communicator will send
these codes if Point ID is enabled and any sensor
has a low battery or trouble condition. The factory
settings are listed, along with a blank area to write
in the new installation values.
Use program Steps #234 - 257 to change the 4 by 2
Point ID trouble reporting codes.
NOTE: Be careful not to duplicate codes unless the
Central Station requires specifi c codes for certain
types of sensors.
STEPS #234-257
Any value from 0-99 can be programmed for each
event using these steps (enter “0” to stop an event
from reporting).
0 - 99 FOR SENSOR
ALARM CODE
(0 = NO REPORT)
PROGRAMMING STEPS
#210 TO #221
PROGRAM
STORE PROGRAM
2
ABC
0 - 99 FOR SENSOR
TROUBLE CODE
(0 = NO REPORT)
PROGRAMMING STEPS
#234 TO #245
PROGRAM
STORE PROGRAM
2
ABC